Profibus DP Marin SHF1
Variant: |
Shielded BUS-cable, IEC 61158-2, certified for use in ship- and offshore installations. The cable is low smoke and zero halogen,
oil- and UV-resistant, AWG 22/7 tinned Cu-conductor, foam PE insulation, filler, AL/Mylar and tinned CU-braid screen, outer jacket SHF1.
Construction
Conductor
0.35 [mm²]
Stranded
Tinned Cu
7 x 0,254 [mm]
AWG 22/7
(0.35mm²)
Screen
Collective
Al/Mylar
Insulation
Foamskin PE
Ø = 2,55 ± 0,05 [mm]
Colour code
Red, green
Filler
PP
Screen
Tinned Cu-braid
> 80 [% coverage]
Jacket
Black
SHF1
(other colours on request)
O.D.
8 [mm]
Weight
80 [kg/km]
Jacket marking
NEK Kabel - Profibus DP Marin - 1x2xAWG22/7 SHF1 - DNV-GL - IEC 60332-3-22 - batch no - <****meter> - <dd/mm/yyyy>
Specifications
Operating temperature
-40 - +80 [°C]
Temperature @ installation
-20 - +60 [°C]
Operating voltage
100
[V]
Test Voltage
1
[kV-DC]
Conductor resistance
≤55 [Ω/km]
Insulation resistance
≥1 [GΩ x km]
Capacitance
30 [pF/m]
at 1kHz
Impedance
150 ± 15 [Ω] at 3-20MHz 185 ± 18,5 [Ω] at 38,4MHz 250 ± 25 [Ω] at 9,6MHz
Attenuation
≤ 45[dB/m] at 16 MHz ≤ 22[dB/m] at 4 MHz ≤ 5[dB/m] at 38,4 kHz ≤ 3[dB/m] at 9,6KHz
Min. bending radius flexible
20 [x outer diam]
Min. bending radius installed
10 [x outer diam]
Norms
Halogenfree, max content corrosive and toxic gases
IEC 60754-1, 2
Material properties, insulation and sheath
SHF1
Design and testing standards
IEC 61158-2
IEC 60092-360
Flame retardant
IEC 60332-1
Fire retardant
IEC 60332-3-22 Cat.A
Oil and fuel, hydrocarbons resistant
IEC 60811-2-1
IRM 902
23ºC / 7 days, 70°C / 4h
Smoke emission
IEC 61034-2
Field bus specifications
IEC 61784 - 1 - 2
IEC 61158 ed. 6
UV-resistant
UL 1581 (300H)
Certification
DNV-GL
Part No.
Black: 1091092 Blue: 3010005 Purple: 3010006
Updated
Date | Rev. | Description |
---|---|---|
5.4.2019 | 1 | DNV-GL Approved |
15.4.2019 | 2 | Additional information |
24.05.2019 | 3 | Adding part numbers |
24.08.2020 | 4 | Temp.range |