LanMarin-Fire

LanMarin® Fire Cat 7

Variant:

LAN-cable for use in areas where the requirement for cables operating during fire is needed. 

Construction

Conductor
Stranded
Bare Cu
AWG 23/7
Insulation
Fire resistant material
+ Mica tape
No. of pairs
4
Colour code
IEC 60189-2
Individual Screen pairs
Al-/polyester tape
Overall Screen
Tinned Cu-braid
Diam. of strands: ≥0,10mm
Outer Jacket
Grey
LSZH
UV-resistant
SHF1
O.D.
10,5 [mm]
Weight
130 [kg/km]

Specifications

Test Voltage
1
[kV-DC]
or 1 [kV-AC] for 1 minute
Conductor resistance
≤ 69,5 [Ω/km]
Insulation resistance
≥ 5000 [MΩ x km]
Capacitance
55 [pF/m]
at 800 - 1000 Hz
Impedance
100 ± 5
[Ω]
at 100MHz

Norms

Halogenfree, max content corrosive and toxic gases
IEC 60754-1, 2
Material properties, insulation and sheath
NEK 606
Flame retardant
IEC 60332-1
Toxic gases max.
EN 50305 9.2
Fire retardant
IEC 60332-3-22
Fire resistant
IEC 60331-23
EN 50200-PH15
UV-resistant
ASTM D 2565 92A
Part No.
2030000

Attenuation

Frequency (MHz) Attenuation Max. (dB/100m) Return Loss (dB/100m) NEXT (dB/100m) PS-NEXT (dB/100m)
1 3,02 - 78 75
4 5,61 23,0 78 75
10 8,78 25 78 75
16 11,12 25 78 75
20 12,44 25 78 75
31,25 15,62 23,33 78 75
62,5 22,32 20,74 75,46 72,46
100 28,53 18,99 72,40 69,40
155 35,96 17,35 69,55 66,55
200 41,20 16,40 67,88 64,88
300 51,28 15,60 65,24 62,24
600 75,15 15,60 60,73 57,73